Cummins 900kw DieselGenerator Set
Optional Configurations for Cummins 900kW Diesel Generator Set
- ATS Automatic Load Transfer Cabinet
- Automatic Paralleling Cabinet
- Container-type Generator Set
- Mobile Trailer-type Power Station
- Rainproof-type Generator Set
- Soundproof-type Mobile Power Station
- Remote Microcomputer Interface
- 500-1000 Hour Operation Spare Parts

| Configuration selection |
| Product advantages |
| Product Description |
| GENERATOR SET TECHNICAL PARAMETERS | |||
| Model: | Voltage Regulation: | ≥±5% | |
| Prime Power (KVA/KW): | 1125/900 | Voltage Regulation, Stead State: | ≤±1% |
| Standby Power (KVA/KW): | 1237.5/990 | Sudden Voltage Warp: | ≤+25% |
| Rated Current (A): | 1800 | Sudden Voltage Warp: | ≤-20% |
| Power Factor (COSΦ): | 0.8 lagging | Voltage Stable Time: | ≤6S |
| Rated Frequency: | 50Hz | Voltage unbalance: | ≤1% |
| Starting Method: | 24V DC start | Frequency Regulation, Stead State: | ≤5% |
| Dimensions (mm): | 4400×2100×2300 | Frequency Waving: | ≤1.5% |
| Weight (kg): | 9500 | Frequency Recovery Time: | ≤5S |
| DIESEL ENGINE DATA | |||
| Brand: | Cummins | Compression Ratio: | 13.9:1 |
| Model: | KTA38-G9 | Fuel Consumption Rate (g/kwh): | 208 |
| Rate Power (kw): | N/A | Rated Speed: | 1500/RPM |
| Standby Power (kw): | 1089 | Air Intake System: | Turbocharger |
| Number of Cylinders: | 12 | Type: | Four-stroke、Direct injection |
| Displacement (L): | 37.8 | Cooling Mode: | Closed water cooling |
| Bore/Stroke (mm): | 159/159 | Start Mode: | Electric starting |
| ALTERNATOR DATA | |||
| Brand: | HAOLIAN | Power Factor (COSΦ): | 0.8 lagging |
| Model: | HL-900 | Insulation Class: | H |
| Rated Power (KVA): | 1125 | Protection Class: | IP22 IP23 |
| Rated Voltage (V): | 400/230 | Voltage Regulation Method: | AVR (Automatic Regulation) |
| Number of bearing: | 1 | Wiring Method: | 3 phase and 4 wires,"Y" type connecting |






FAQs Related to Cummins 900kW Diesel Generator Set:
Q: What practical optional configurations are available for the Cummins 900kW diesel generator set? What benefits do these configurations provide?
Q: Will the unit's performance be affected when operating in high-temperature or high-altitude environments? Are there countermeasures?
A: It features special designs for harsh environments. For high temperatures, enhanced radiators and fuel cooling systems can be configured; for high altitudes, air intake optimization and fuel injection parameter adjustment reduce power loss. These measures ensure stable operation in complex environments.
Q: Does the Cummins 900kW diesel generator set support parallel operation of multiple units? How stable is the operation after paralleling?
A: It supports parallel operation of multiple units with a dedicated paralleling control system. This system achieves uniform load distribution through precise synchronization adjustment, ensuring stable voltage and frequency after paralleling, meeting large-capacity power supply needs with reliable operation.